Features
|
Benefits
|
Choice
of common mode noise reduction characteristic model |
Reduces
common mode and normal mode noise
|
K-13
rated
|
Designed
to handle the most intense non-linear load application |
Small
footprint
|
Saves
valuable space. Fast, easy installation
|
Exclusive
shielding
|
Protects
sensitive loads from surges and spikes and prevents back feeding of
noise from line to load |
UL
and cUL listed
|
Low
leakage current (full safe) allows use of products in hospitals and
medical labs |
Over
temperature protection
|
Protects
the unit and load in case of fire |
| Input voltage 208,480 VAC |
yes |
| Output voltage 208Y/120Y |
yes |
| K-13 rated |
yes |
| Common mode noise |
146dB |
| Normal mode noise |
60dB |
| Overload capacity |
500% for 1 cycle, 200% for
30 seconds |
| Dielectric strength |
2,500 VAC minimum |
| Frequency |
47-53Hz for 50Hz model /
57-63Hz for 60Hz model |
| Impedance |
3-5% typical |
| Efficiency (output voltage) |
95% typical |
| TAPS |
6 at 2.5% / 2 above
nominal / 4 below nominal |
| Input voltage range |
+/-10% of nominal rated voltage |
| Load regulation |
3.5% or less from no load
to full load at unity power factor |
| Harmonic distortion |
1% maximum |
| Insulation resistance |
100 megohms minimum from
windings to core |
| Electro-magnetic interference |
0.1 gauss maximum measure
at 36 inches |
| Warranty |
5 years |