Characteristics
Home > Products > Three Phase Systems > Sinewave > Characteristics
 
Model SW20 SW30 SW45 SW60 SW90 SW120
Per phase compensation capacity 20 A rms 30 A rms 45 A rms 60 A rms 90 A rms 120 A rms
Compensation capacity in the neutral (1) 60 A rms 90 A rms 135 A rms 190 A rms 270 A rms 360 A rms
AC supply input
Nominal voltage (2) 400 V - 20 + 15%
Nominal frequency 50 Hz, 60 Hz, ± 8%
Number of phases 3 phases with or without neutral
(operation is possible on unbalanced or single phase loads)
Current transformers rating from 300/1 to 4000/1
Technical specifications
Harmonic current compensated Orders 2 to 25, global compensation or specified harmonics
Rate of harmonic reduction THDI load/THDI network greater than 10 at nominal conditioner capacity
Current compensation of cosine phi Up to 1.0
Response time < 40 ms
Overload Limitation to nominal current, continuous operation within these limits
Inrush current < twice nominal peak current
Losses 1000 W 1300 W 2100 W 2600 W 4200 W 5200 W
Noise level (ISO 3746) < 55dBA < 55dBA < 60dBA < 60dBA < 65dBA < 65dBA
Colour RAL 9002
Environmental conditions
Operating temperature 0 to 40°C continuous, < 25°C recommended
Relative humidity 0 to 95% no condensing
Operating altitude < 1000 m
Reference standards
Construction and safety EN 50091-1
Design IEC 146
Protection IP 30 according to IEC 529
Electromagnetic compatibility
Conducted and radiated emission En 55011 Class A
Immunity to electrostatic discharges IEC 1000-4-2 level 3
Immunity to electromagnetic fields IEC 1000-4-3 level 3
Immunity to impulse waves IEC 1000-4-4 and IEC 1000-4-5 levels 4
Dimensions and weight
W x H x D (mm)
(Inches)
540 x 680 x 280
21.4 x 27 x 11.1
590 x 780 x 325
23.4 x 30.9 x 12.9
1180 x 780 x 325
46.8 x 30.9 x 12.9
Weight (kg)
(lbs)
65
143
110
242
220
484

(1) maximum capacity on PC type load on balanced 3-phase network
(2) 208 V, 220 V and 480 V voltages are available upon request