Standard functions
Double conversion topology, Class VFI,
conforming to IEC Standard 62040-3,
with static contactor and manual
bypass for maintenance
LCD display screen and mimic diagram
Automatic battery test facility
1 U-Talk Port for computer connexion,
1 slot available for voltage free contact
card
Options
Dry contacts card for relaying alarms
Network Management link Pack for
remote management and shutdown
Installation guide

Net weights of the UPS
and battery enclosures (kg)
|
15 / 20 kVA |
30 kVA |
| UPS only and XL version (for long backup time) |
308 |
320 |
| UPS + 5' integral batteries |
437 |
487 |
| UPS + 10' integral batteries |
475 |
621 |
| UPS + 15' integral batteries |
505 |
|
| 15' battery enclosures |
|
555 |
Choice of cables (in mm2)
|
15 kVA |
20 kVA |
30 kVA |
| Input for circuit 1 |
3x10 |
3x10 |
3x25 |
| Inputs for circuit 2 and load |
2x25 |
2x35 |
2x70 |
| Batteries |
Integrated |
Integrated |
Integrated
except 15’ / 2x25 |
| Choice of fuses: currents(1) in A |
Current for circuit 1
(with battery recharging) |
26 A |
37 A |
52 A |
| Currents for circuit 2 and load |
65 A |
87 A |
130 A |
| Battery currents |
Integrated |
Integrated |
Integrated except 15’ |
1 – 3-phase 400 V and single-phase 230 V voltages
Commercial references

|
15 kVA |
20 kVA |
30 kVA |
UPS only |
WWCUV150
|
WWCUV111
|
WWCUV104
|
| UPS only XL (for backup times > 15 min) |
WWCUV151 |
WWCUV121 |
WWCUV114 |
| UPS + 5’ integral batteries |
WWCUV152 |
WWCUV101 |
WWCUV105 |
| UPS + 10’ integral batteries |
WWCUV153 |
WWCUV102 |
WWCUV106 |
| UPS + 15’ integral batteries |
WWCUV154 |
WWCUV103 |
|
| A15’ battery enclosures |
|
|
WWCBV001 |
| Empty battery enclosures |
|
WWCBV011 |
|
| Dry contacts cards |
|
WWCCV001 |
|
| Network Management link |
|
66077 |
|
Technical characteristics

|
15 kVA |
20 kVA |
30 kVA |
| Active power output (kW) |
12 |
16 |
24 |
| Inputs |
Voltage range (circuit 1) |
From 342 V to 457 V, 3 phases |
| Voltage range (circuit 2) |
From 198 V to 264 V, 1 phase |
| Frequencies |
50 or 60 Hz ±5 % |
| Outputs |
Voltages (user-definable) |
220/230/240 V, 1 phase |
| Frequencies |
50/60 Hz ±0,001Hz |
| Permissible overloads |
150 % for 1 minute, 125 % for 10 minutes |
| Voltage distortion (Ph/Ph) |
THDU < 2 % on a linear load |
| Peak factor |
3:1 |
| Efficiency |
Up to 90 % |
| Batteries |
Type |
Sealed lead-acid batteries |
| Recharging time |
8 hours for 80 % battery output (10 minutes) |
| Battery capacities |
5, 10 and 15 minutes |
Recommended operating
temperatures |
15° to 25 |
| Environment |
Evaluated losses (in kW) |
1,16 |
1,55 |
2,33 |
| Noise level |
(dBA) 58 |
| Operating temperatures (°C) |
0° to 40° |
| Storage temperatures (°C) |
-10° to 60° |
| Protection index |
IP21 |
| Colour |
RAL 9001 |
| Environment |
Construction |
IEC 62040-1-2, IEC 60950, EN62040-1-2 |
| Topology and performance characteristics |
IEC 62040-3, 62040-3 |
| Design and manufacture |
ISO 14001, ISO 9001, IEC 60146 |
| EMC |
IEC 62040-2 |
|