Products Services Support Selectors Download About us International
Galaxy 1000 PW
Overview
Quality & Services
Characteristics
Brochures
MGE services
 
Related Links
UPS Selector
Are you at risk?
Support
Services
White papers
Home Email Printer friendly
 
Contact us Site map
GALAXY 1000 PW > Characteristics
Home > Products > Three Phase Systems > Galaxy 1000 PW > Characteristics
 
Electrical characteristics
Rated power (Pn) in kVA 30 40 60 80
UPS input (mains 1)
Voltages 380 V - 10% (option -15%) to 415 V + 15 % 3-phase
Frequency 50 or 60 Hz +/- 10%
Power factor 0.95 with filter
Distortion THDI < 4% with THM filtering
Bypass input (mains 2)
Voltages 220 or 230 V or 240 V +/- 10 % single-phase
Frequency 50 or 60 Hz +/- 10%
UPS output
Steady-state voltage 220 - 230 - 240 V single-phase
adjustable +/- 3%
Frequency 50 or 60 Hz +/- 0.5 Hz
Synchronisation threshold with bypass 0.25 to 2 Hz in 0.25 Hz steps
Voltage transients (dynamic performance) +/- 2% for load change of 0% to 100% and 100% to 0%
Permissible overload duration 125% for 10 minutes, 150% for 1 minute
Short-circuit current (without transfert to bypass) > 2.3 In for 1s
Distortion at linear load THDU < 2%
Distortion at Pn non-linear load THDU < 3%
Battery
Backup time 8, 10, 15, 20, 30 and 60 min, other values on request
Types Sealed lead acid (service life 5, 7, 10 years) vented lead acid, Nickel Cadmium
Voltages Floating : 423 to 463 V
Voltage regulation Temperature correction
Overall UPS Efficiency at In
Normal mode up to 92 %
Eco mode up to 97 %
Temperatures
UPS Operation - 5° C to 40° C, 40° for 8 hours maximum
Storage With battery : - 20° C to + 45° C,
Without battery : - 20° C to + 70° C
Battery operation Optimum between + 15° C and + 25° C The life of sealed batteries is halved for each 10° C above this range
General specifications
Noise level as defined by ISO 3746 < 65 dBA
Standards
Design and performances IEC 146, ENV 50091-3
Safety EN 50091-1, IEC 60950 / EN 60950
EMC EN 50091-2, IEC 61000-2-2, IEC 61000-4


Dimensions

Rated power (Pn) in kVA
(power factor 0.8)
30 40 60 80
UPS module dimensions and weights
Width (mm)
1015
Depth (mm)
825
Heigth (mm)
1900
Weight (kg) 600 600 650 650
Battery cabinet dimensions and weights (example for 10 min back-up time)
Height (mm)
1900
Depth (mm)
840
Width (mm)
715
1 015
Weight (kg) 530 675 845 1 100


Top Back