| Rated power (Pn) in kVA |
30 |
40 |
60 |
80 |
| UPS input (mains 1) |
| Voltages |
380 V - 10%
(option -15%) to 415 V + 15 % 3-phase |
| Frequency |
50 or 60 Hz
+/- 10% |
| Power factor |
0.95 with filter |
| Distortion |
THDI < 4%
with THM filtering |
| Bypass input (mains 2) |
| Voltages |
220 or 230 V
or 240 V +/- 10 % single-phase |
| Frequency |
50 or 60 Hz
+/- 10% |
| UPS output |
| Steady-state voltage |
220 - 230 -
240 V single-phase
adjustable +/- 3% |
| Frequency |
50 or 60 Hz
+/- 0.5 Hz |
| Synchronisation threshold with bypass |
0.25 to 2 Hz
in 0.25 Hz steps |
| Voltage transients (dynamic performance) |
+/- 2% for load
change of 0% to 100% and 100% to 0% |
| Permissible overload duration |
125% for 10
minutes, 150% for 1 minute |
| Short-circuit current (without transfert
to bypass) |
> 2.3 In
for 1s |
| Distortion at linear load |
THDU < 2% |
| Distortion at Pn non-linear load |
THDU < 3% |
| Battery |
| Backup time |
8, 10, 15, 20,
30 and 60 min, other values on request |
| Types |
Sealed lead
acid (service life 5, 7, 10 years) vented lead acid, Nickel
Cadmium |
| Voltages |
Floating : 423
to 463 V |
| Voltage regulation |
Temperature
correction |
| Overall UPS Efficiency at
In |
| Normal mode |
up to 92 % |
| Eco mode |
up to 97 % |
| Temperatures |
| UPS Operation |
- 5° C to
40° C, 40° for 8 hours maximum |
| Storage |
With battery
: - 20° C to + 45° C,
Without battery : - 20° C to + 70° C |
| Battery operation |
Optimum between
+ 15° C and + 25° C The life of sealed batteries is
halved for each 10° C above this range |
| General specifications |
| Noise level as defined by ISO 3746 |
< 65 dBA |
| Standards |
| Design
and performances |
IEC 146, ENV
50091-3 |
| Safety |
EN 50091-1,
IEC 60950 / EN 60950 |
| EMC |
EN 50091-2,
IEC 61000-2-2, IEC 61000-4 |