| Electrical
characteristics |
| Rated output in kVA (power factor=0.8) |
160 |
200 |
250 |
300 |
400 |
500 |
600 |
800 |
| Input |
| Mains 1 voltage |
380 V or 400V or 415 V ± 10 % 3 phase (1) |
| Mains 2 voltage |
380 V or 400V or 415 V ± 10 % 3 phase + neutral (1) |
| Frequency |
50 or 60 Hz ± 5 % |
| Output |
| Steady-state voltage |
380 V or 400V or 415 V ± 0.5 % 3 phase + neutral |
| Voltage transients |
< ± 5 % for a load change from 0 % to 100 % and 100
% to 0 % |
| Frequency |
50 or 60 Hz ± 0.5 % |
| Distortion |
< = 2 % for a 100 % linear load, < = 3 % for a 100
% non-linear load |
| General |
| Battery runtime |
10 or 15 minutes, other values available |
| Efficiency (in %) at full rated load |
94 % |
94.5 % |
| Overload |
150 % for 1 minute, 125 % for 10 minutes |
| Accoustic noise (in dBA as per ISO 37 46) |
< = 68 |
< = 69 |
< = 72 |
< = 75 |
| Operating temperature range |
- 5 °C to + 40 °, + 40 ° for 8 hours maximum
|
| Standards
|
IEC 146 - 4, IEC 801 - 2/3/4 or IEC 1000 - 4 - 2/3/4
EN 50 091 - 1, IEC 1000 - 2 - 2, CE Marking |
| UPS dimensions
and weight |
| Rated input in kVA |
160 |
200 |
250 |
300 |
400 |
500 |
600 |
800 |
Dimensions (mm)
Width |
1600 |
1600 |
1600 |
1600 |
1600 |
3600 |
3600 |
4250 |
| Weight (kg) |
1390 |
1390 |
1620 |
1620 |
2030 |
3350 |
3350 |
4300 |
| Dimensions (mm) H x D |
1900 x 840 |