Products Services Support Selectors Download About us International
Galaxy 3000
Characteristics
Features & Benefits
 
Related Links
Brochures & Manuals
Software
Pictures
Visio™ Shapes
White papers
Home Email Printer friendly
 
Contact us Site map
Galaxy 3000 - Characteristics
Home > Products > Three Phase Systems > Galaxy 3000 > Characteristics
 
Rated power (kVa)
10
15
20
30
Actived power
8
12
16
24
Normal AC input
Rated voltage 380 -400 -415- 3-phase + neutral
Voltage range 250 V min to 440 V max
Frequency 50/60 Hz
Frequency window 47 to 63 Hz
Power factor > 0.99
Current distortion (THDI) < 3% (2)
Output
Voltage under steady-state conditions 380 -400 -415 V +/-1% - 3-phase + neutral
Frequency 50 or 60 Hz +/- 1%
Voltage transients Voltage distortion
Voltage distortion
+/- 3% for 0% to 100% and 100% to 0% load step changes
THDU< 2% ph-ph and ph-n for linear loads
Permissible overload THDU<+/- 3% ph-ph and ph-n for non-linear loads
120% for 1-5 min., 150% for 1 second
Overall efficiency
  Up to 97% in ECO mode
Batteries
Backup time 10 minutes to 8 hours, 5 or 10-year service live
Standard backup time (5-year batteries) 10/12 min (3) 10/12 min (3) 10/12 min (3) 9/10.5 min (3)
Standard backup time (10-year batteries) 12/14 min (3) 7/8.5 min (3) 12/14 min (3) 7/8.5 min (3)
Environment
Colour RAL 9002 or metallised grey, blue or green
Ambient temperature 0° to 40° C, 20° to 25°C recommended, 0° to 30° C continuous
Noise level (dBA)
< 50
< 50
< 53
< 53
Standards
Construction and safety IEC 62040-1, IEC 60950, EN 50091-1
Performance and topology IEC 62040-3, EN 50091-3
Design and manufactering ISO 14001, ISO 9001
EMC IEC 62040-2 and EN 50091-2 level B, EN 55011 and EN 55022 level B
Harmonics IEC 61000-3-2/4
Certification and marking TÜV, CE
Galaxy 3000 UPS dimensions and weights 
Widht (mm)
655
670
Height (mm)
1420
1600
Depth (mm)
565
685
Weight (kg)
330
380
470
570
Galaxy 3000 battery cabinet dimensions 
Widht (mm)
650
850
Height (mm)
1420
1600
Depth (mm)
565
685

(2) for source THDU < 2%.
(3) backup time for linear loads with power factor = 0.8/ for standardised non-linear load
Top Back