Nominal rating (kVA) PF = 0.8
20
30
40
60
80
100
120
Normal AC supply input
Input voltage range 250V (1) to 470V three phase
Inputs Mains 1 and Mains 2 Separate or common
Frequency 50Hz / 60Hz +/- 8%
Input current total harmonic distortion (THDI) < 3%
Input power factor > 0.99
Bypass system input
Nominal input voltage 340V to 470V Three phase + neutral
Frequency 50Hz / 60Hz +/- 8%
Output
Output voltages 380V - 400V - 415V +/-3% three phase + neutral
Voltage regulation +/- 1%
Frequency 50Hz / 60Hz
Over load 150% 1 minute, 125% 10 minutes
Output voltage total harmonic distortion
(on non linear loads)
THDU < 2%
Max load crest factor 3:1
Batteries
Backup time 5 minutes to 8 hours with standard internal charger
Type Sealed lead acid, open lead acid, nickel cadmium
Overall efficiency
Double conversion mode up to 94%
Economy mode up to 97%
Environmental conditions and noise
Storage temperature -25°C to +45°C
Operating temperature up to 40°C (2)
Operating altitude 1000 m
Paralleling
Modular up to 6 modules
Standards and approvals
Performance and safety IEC/EN 62040-1, IEC/EN 60950
Performance and design IEC/EN 62040-3
Design and manufacturing ISO 14001, ISO 9001, IEC 60146
EMC immunity IEC 61000-4-2 to 6
EMC emissions IEC 62040-2 Category C3
Approvals TÜV - LCIE - CEM - CE Mark
Dimensions and weight (depth = 850 mm and height = 1900 mm)
 
20
30
40
60
80
100
120
UPS without batteries (width in mm) 710
Weight
400kg
520kg
UPS + built-in batteries (width in mm) 1110
From 5 minutes to 35 minutes(3)
  738kg
888kg
1050kg
From 10 minutes to 50 minutes(3)
732kg
888kg
975kg
From 15 minutes to 90 minutes(3)   975kg    
From 20 minutes to 110 minutes(3) 738kg 888kg      
From 30 minutes to 120 minutes(3) 888kg 975kg      
Battery cubicles (width and weight) 1110
From 5 minutes to 35 minutes(3) (width in mm)   710
From 5 minutes to 35 minutes(3) (weight)   885kg 980kg
From 10 minutes to 50 minutes(3) (width in mm)   710 1110
From 10 minutes to 50 minutes(3) (weight)   885kg 1142kg 1307kg
From 15 minutes to 80 minutes(3) (width in mm)   710 1110 1110 2x1110
From 15 minutes to 80 minutes(3) (weight)   885kg 1142kg 1307kg 1764kg
From 30 minutes to 120 minutes(3) (width in mm) - 710 1110 2x710 710+1110 2x1110
From 30 minutes to 120 minutes(3) (weight) - 882kg 1307kg 1764kg 2439kg 2742kg

(1) : At 70% nominal load.
(2) : There is a risk of premature battery ageing above 25°C.
(3) : From 100% to 30% nominal load.