Nominal power output
(kVA at PF = 0.8) |
20 |
30 |
40 |
50 |
60 |
80 |
100 |
120 |
| Active power output (kW) |
14 |
24 |
32 |
40 |
48 |
64 |
80 |
96 |
| UPS input |
| Voltages |
380-400-415 V +/- 10 % - three-phase (adjustable to +/- 15 %) |
| Frequency |
50
or 60 Hz +/- 10% |
| Power factor |
up to 0.95 |
| Current Distortion (THDI) |
< 4% |
| Bypass supply input |
| Voltages |
380-400-415 V +/- 10 % - three-phase + neutral |
| Frequency |
50 or 60 Hz
+/- 10% |
| Output |
| Configured Ph/Ph voltages |
380-400-415 V +/- 1 % - three-phase + neutral |
| Frequency |
50 or 60 Hz +/- 0.05 %, adjustable |
| Permissible overloads |
150 % 1 minute, 125 % 10 minutes |
| Voltage distortion |
THDU < 1.5 % Ph/Ph, < 2 % Ph/N with linear load(1)
THDU < 3 % Ph-Ph and Ph-N with non-linear load(1) |
| Crest factor |
3:1 |
| Battery |
| Battery discharge times |
8, 10, 15, 20, 30, 60 minutes, other values on request |
| Types |
Sealed lead acid
(service life 10/12 years) |
| Overall UPS efficiency at
In |
| Normal mode (%) |
up to 91% |
| Eco mode (%) |
up to 96% |
| Environment |
| Losses to be dissipated(2) (in kW) |
2 |
2.8 |
3.6 |
3.9 |
4.9 |
6.6 |
8.3 |
10.3 |
| Storage |
- 25°C to + 45°C (with batteries) |
| Operation |
0°C to 35°C (40°C for a period of 8 hours) |
| Accoustic Noise (dBA) |
58 |
58 |
58 |
60 |
60 |
62 |
64 |
65 |
| Technical standards |
| Design & Manufacture |
ISO 14001, ISO 9001, IEC 60146 |
| Construction & Safety |
IEC 62040-1, IEC 60950, EN 50091-1 |
| Performance and topology |
IEC 62040-3, EN 50091-3 |
| EMC |
IEC 62040-2 and EN 50091-2 level B |
| Certifications and identification markings |
TÜV, CE |
| Dimensions and weights of the UPS (depth = 825 mm and height = 1900 mm) |
| Width (mm) |
715 |
715 |
715 |
715 |
715 |
1015 |
1015 |
1015 |
| Weight (kg) |
550 |
550 |
550 |
600 |
600 |
905 |
905 |
905 |
| Battery compartment (depth = 825 mm and height = 1400 mm) |
10-minute autonomy Width (mm) |
715 |
715 |
715 |
715 |
1015 |
- |
- |
- |
Weight (kg) |
480 |
500 |
640 |
670 |
820 |
- |
- |
- |
30-minute autonomy Width (mm) |
715 |
1015 |
1730 |
1730 |
2445 |
- |
- |
- |
Weight (kg) |
660 |
945 |
1340 |
1650 |
2030 |
- |
- |
- |
| Battery compartment (depth = 825 mm and height = 1900 mm) |
10-minute autonomy Width (mm) |
715 |
715 |
715 |
715 |
715 |
1015 |
1015 |
1430 |
Weight (kg) |
500 |
530 |
675 |
690 |
845 |
1100 |
1370 |
1730 |
30-minute autonomy Width (mm) |
715 |
715 |
1430 |
1430 |
1730 |
2030 |
2030 |
2745 |
Weight (kg) |
695 |
945 |
1390 |
1685 |
1930 |
2475 |
2765 |
3820 |
1: Conforming to technical standards EN50091-3 / IEC 62040-3. 2: The indicated losses are produced by the UPS at nominal
load with the battery in floating mode.