Characteristics
Home > Products > Three Phase Systems > Upsilon STS > Characteristics
 
Ratings (A)
30
60
100
160
250
400
600
800
1200
1600
2000
Source Inputs
Rated voltage
380 V (± 35%) - 400 V - 415 V (± 20%)
Rated frequency
50 Hz or 60 Hz (± 10%)
Number of phases
3 ph + N + Earth or 3 ph + N
3 ph + Earth
 
Operation
Permissible overloads
110% 15 minutes - 150% 2 minutes
- 200% 20 ms
 
Contact us
Efficiency (linear load & pf = 0.8)
0.99
 
Contact us
Transfer time
3 ms (typical) / 5ms (maxi)
 
Contact us
Environment
Air flow (m3/hr)
350
1600
2300
 
Contact us
Operation
0°C to 40°C
 
Storage temperature
-20°C and +40°C
 
Noise level (dBA)
< 60 dB
 
Standards
Manufacturing and safety
EN 50091-1/ IEC 62040, IEC 60950,
EN 50081-2, EN 50178, EN 50082-2
EMC
EN 50091-2
Certifications
TÜV, CE
Dimensions and weight
Height x Width (mm)
1400 x 600 or 1900 x 715
1900 x 715
1900 x 2030
Contact us
Depth H = 1400 (mm)
500
-
-
Contact us
Depth H = 1900 (mm)
825
825
825
Contact us
Weight (kg)
for H = 1400 mm
193
130
160
-
Contact us
Weight (kg)
for H = 1900 mm
215
225
327
845
Contact us