![]() |
Galvanic Isolation | |||
| Tech Notes 10 | ||||
| |
Mandatory for the centralized protection of computer networks Computers generate leakage current
The increase in the number of computers
and servers connected to an electrical installation is at the root of
a sticky problem, the accumulation of leakage currents. Even if each computer,
considered individually, complies with the standard, there is nothing
to guarantee that once several of them are installed in an office, they
will continue to comply. Several computers or other electrical devices,
connected to the same circuit-breaker, add up their respective leakage
currents. Here, the relevant standard for an electrical installation (NFC
15-100 in France for example) specifies that the total amount may under
no circumstances exceed 30 mA. This value is reached with ten computers.
Over and above this value, the differential circuit-breaker must trip
in order to avoid any risk of electrocution in the event of a fault occurring
on one of the devices. A real threat In Europe, some installation standards stipulate that a circuit-breaker should be fitted for every six wall sockets. This is intended to reduce the risks. However, no standard prohibits the use of multi-socket adapters which enable end-users to multiply the number of sockets protected by the same circuit-breaker by a factor of 4 or 5!
The risk is exacerbated by the fact that the circuit-breaker may trip
for values as low as 15 mA in order to guarantee tripping at 30 mA. In
this case, the risk starts with 5 computers connected to the same circuit-breaker.
Overcoming the problem There are two possible solutions: the first involves
asking a specialist to change the electrical installation in order to
support high leakage currents. This approach may prove costly, as cables
with larger cross-sections will need to be fitted, replacing the existing
ones.
As its name suggests, this function completely isolates the UPS output from its input. The only leakage current detected by the head circuit-breaker is the current produced by the UPS itself, that is around 1.5 milliamperes for a Pulsar EX. Galvanic isolation is particularly recommended for a UPS protecting more than 5 to 7 workstations: connected to a wall socket, the UPS allows you to protect an unlimited number of stations without having to worry about disturbances while guaranteeing service continuity.
Which UPSs in the Pulsar range implement galvanic isolation? Pulsar EX15 to EX40 UPSs have the advantage of offering
continuous, high-frequency isolation.
The UPSs with the highest power ratings, such as the
Comet range for computer rooms, require a visit by an electrician. The
electrician will ensure that the circuit-breaker is appropriately rated.
Pulsar ES and ESV UPSs, which are designed for distributed protection,
do not implement the isolation function. We therefore advise against connecting
more than 5 stations to these products. The Pulsar ESV 20, which is theoretically
capable of protecting from 15 to 20 computers at a time, is actually recommended
for protecting one mini-computer and its immediate peripherals.
Can a UPS sometimes impair the quality of an electrical installation? Yes! From an electrical point of view, a UPS is a power supply, just like a computer or a printer. It consequently generates leakage current (about 1.5 milliamperes) which is added to the sum of the leakage currents generated by the protected computer systems, unless there is an isolation system between the UPS input and output. Adding a UPS may be enough to exceed the 15 mA barrier above which the protection on the electrical installation's main circuit-breaker may trip, putting the lights out for all the users. Galvanic isolation of On-line technology All
the On-line UPSs on the market do not offer this function, even if this
was the case ten years ago.
|
||
|
|||||||